Category: DC Load Banks / Battery Capacity Testers
Constant Current DC Load Bank 20–40 Vdc 0–150 Amp / 40–60 Vdc 0–300 Amp
The only true way to be certain if your stationary batteries will perform to specification under load is to capacity test the batteries regularly.
NERC standard PRC-005-2 requires that vented lead acid and nickel cadmium (NiCd) systems be discharge tested every six (6) years and valve regulated lead acid (VRLA) batteries every three (3) years. IEEE recommends load testing stationary flooded/vented lead acid and NiCd stationary batteries every five (5) years and VRLA batteries every 12–18 months.
The SBS-4830S constant current load bank is an affordable way to perform easy and accurate load tests, including IEEE450 (vented lead acid), IEEE1106 (NiCd) and IEEE1188 (VRLA) load tests.
SBS load banks are quick and easy to set up. The SBS-4830S load bank includes a touch screen to set test parameters and display voltage, current and amp hours (Ah) removed from the string during the test. Since this is a constant current load bank, the user also does not have to adjust the current during the load test.
These load banks come standard with multiple adjustable stop points and built-in protection to ensure that the batteries are never damaged due to over-discharge.
Dimensions | 26 x 9 x 16 in. |
---|---|
Weight | 40.000000 |
Power Supply(s) |
SBS-4830S uses DC power supply (from tested battery) 125 and 250 Vdc units use AC power supply (110 Vac 60 Hz) |
Display Type | LCD (128 x 64 pixels) |
Protection | Overheat / Overload / Over voltage protection with audible alarm and screen warning |
DC Volt Range |
20–40 Vdc 40–60 Vdc |
DC Current Range |
0–150 A 0–300 A |
DC Cables | Included, 9 ft. long |
Input |
During discharge: real time voltage / current / test time / capacity discharged (Ah) User can set: end system voltage / test time / capacity discharged (Ah) |
Test Type | Unit holds the set current throughout the test |
Please Leave Your Product Enquiry Here. We will Get Back To You Soon.